Verification Case 17

View Model     Problem Statement

PRODUCT: AFT Fathom

TITLE: FthVerify17.fth

REFERENCE: Ingersoll-Dresser Pumps, Cameron Hydraulic Data, 18th Ed., 1995, Published by Ingersoll-Dresser Pumps, Page 3-9, 10

FLUID: Water at 68 deg. F

ASSUMPTIONS: N/A

RESULTS:

Parameter Cameron AFT Fathom
Suction head (feet) -5.35 -5.35
Discharge head (feet) 290 289.7
Pump head (feet) 295 295.0
NPSHA (feet) Not provided 27.80

DISCUSSION:

The losses at the pump suction are not explicitly provided in AFT Fathom's library, so the total K factor of 1.57 for the foot valve and long radius elbow is entered as a fitting and loss value in pipe P1. The losses in the discharge piping are in AFT Fathom's library, and are selected as fitting and loss values in pipe P2. The only loss not shown in pipe P2 is the entrance loss at the discharge tank, and that is modeled in the reservoir junction, J3.

The 200 gpm is modeled at the pump as an assigned flow pump.

The AFT Fathom NPSHA prediction is shown in the Pump Summary at the top of the Output window. The suction head is shown as the difference between the EGL inlet and the elevation (23.27 – 28.62) at the pump, J2. It is the negative of the suction lift. The discharge head is shown as the difference between the EGL outlet and the elevation (318.30 – 28.62) at the pump.

Note this model uses fluid properties from the AFT Standard fluid library. The AFT Standard fluid library was updated in AFT Fathom 12, thus the AFT Fathom results will be slightly different for this verification case when compared to previous versions of AFT Fathom.

List of All Verification Models